高压电力电缆金属护套接地系统一旦出现缺陷,将导致电缆金属护层环流异常,长时间运行将损坏电缆绝缘,造成绝缘击穿故障,会严重影响电力电缆的安全稳定运行。以一起高压电缆接地环流异常为例,根据接地系统模型分析护套环流数值,发现A相接地同轴电缆线芯、屏蔽接反是缺陷产生的原因,并分别在带电状态和断电状态下进行了验证。基于此,提出当电缆金属护层环流超过负荷电流80%时,应重点考虑异常情况是否由接地系统接线错误导致,同时,对高压单芯电缆接地系统的接线和验收环节提出改进措施,供工程实践参考。
Abstract:The high voltage power cable metal sheath grounding system abnormality affects the safe and stable operation of power cables.Once the grounding system is defective,it will cause abnormal circulating current in the cable metal sheath which will damage the cable insulation resulting in insulation breakdown in long-term operation.Take a high-voltage cable ground circulation abnormality as an example,the numerical value of the sheath circulation was analyzed according to the grounding system model.It is found that the coaxial cable core and shield connection of phase A grounding were the causes of the defects,which were verified in both on-line and off-line state.Based on this,it is proposed that when the cable metal sheath circulation exceeds 80% of the load current,the fault caused by the wiring error of the grounding system should be suspected.At the same time,improvement measures are put forward for the wiring and acceptance of the single-core high-voltage cable grounding system for engineering practice reference.
[1]中国电力企业联合会.电力工程电缆设计规范:GB 50217-2018[S].北京:中国计划出版社,2018.
[2]能源行业电网设计标准化技术委员会.城市电力电缆线路设计技术规定:DL/T 5221-2016[S].北京:中国计划出版社,2016.
[3]陈小林,成永红,王贤清,等.XLPE电缆地线电流分析与接地改造措施一例[J].高电压技术,2006,32(2):87-88.
[4]王荣亮,王浩鸣,宗红宝,等.高压电缆金属护套接地环流平衡抑制方法分析[J].电力系统及其自动化学报,2019,31(11):108-114.
[5]徐欣,陈彦.220 k V单芯高压电力电缆金属护套感应电流的研究之感应电流的计算和预控[J].电线电缆,2010(5):42-56.
[6]王波,罗进圣,黄宏新,等.220 kV高压单芯电力电缆金属护套环流分析[J].高压电器,2009,45(5):141-145.
[7]邱昊,郑志源.高压单芯电缆交叉互联接地方式优化研究[J].电线电缆,2014(3):33-37.
[8]赵昌鹏,戴斌,李贵山,等.高压单芯电力电缆金属护套环流抑制措施[J].吉林电力,2014,42(1):45-48.
基本信息:
中图分类号:TM75;TM862
引用信息:
[1]于连坤,魏占朋,丁彬,等.电力电缆接地系统缺陷引起环流异常的分析[J].山东电力技术,2020,47(05):26-29.
基金信息:
国家电网公司科技项目“电力电缆潜伏性隐患检测防护与产品施工质量评价技术研究”(SGTJDK00PJJS1800007)
2020-05-25
2020-05-25